Remediation
Containment: keeping mold in the work area
In plain English
Containment is the plastic enclosure around the work. Its job is to stop spores and dust from spreading into the rest of the building while mold is being removed. Protective equipment protects the workers; containment protects the occupants.
Good containment is kept under negative pressure: a HEPA-filtered fan pulls air out of the enclosure and exhausts it outdoors, so air leaks in, not out. You can see whether it's working — the plastic should bow inward on every side. If it billows outward, containment has been lost and work should stop until it's fixed.
EPA describes two levels. Limited containment is a single layer of 6-mil fire-retardant plastic with a slit entry and flap. Full containment is a double layer plus an airlock (decontamination chamber) where workers bag their suits before leaving.
Key points
- Seal supply and return vents, doors, chases and risers inside the work area.
- Negative pressure, exhausted outdoors, with makeup air.
- Plastic bows inward = working. Outward = stop.
- Clean objects before they leave containment.
Official text
EPA 402-K-01-001 — Containment pp. 21–23 Best practice
The purpose of containment during remediation activities is to limit release of mold into the air and surroundings, in order to minimize the exposure of remediators and building occupants to mold. Mold and moldy debris should not be allowed to spread to areas in the building beyond the contaminated site.
The two types of containment recommended in Table 2 are limited and full. The larger the area of moldy material, the greater the possibility of human exposure and the greater the need for containment. In general, the size of the area helps determine the level of containment. However, a heavy growth of mold in a relatively small area could release more spores than a lighter growth of mold in a relatively large area. Choice of containment should be based on professional judgment.[10] The primary object of containment should be to prevent occupant and remediator exposure to mold.
Limited Containment
Limited containment is generally recommended for areas involving between 10 and 100 square feet (ft²) of mold contamination. The enclosure around the moldy area should consist of a single layer of 6-mil, fire-retardant polyethylene sheeting. The containment should have a slit entry and covering flap on the outside of the containment area. For small areas, the polyethylene sheeting can be affixed to floors and ceilings with duct tape. For larger areas, a steel or wooden stud frame can be erected and polyethylene sheeting attached to it. All supply and air vents, doors, chases, and risers within the containment area must be sealed with polyethylene sheeting to minimize the migration of contaminants to other parts of the building. Heavy mold growth on ceiling tiles may impact HVAC systems if the space above the ceiling is used as a return air plenum. In this case, containment should be installed from the floor to the ceiling deck, and the filters in the air handling units serving the affected area may have to be replaced once remediation is finished.
The containment area must be maintained under negative pressure relative to surrounding areas. This will ensure that contaminated air does not flow into adjacent areas. This can be done with a HEPA-filtered fan unit exhausted outside of the building. For small, easily contained areas, an exhaust fan ducted to the outdoors can also be used. The surfaces of all objects removed from the containment area should be remediated/cleaned prior to removal. The remediation guidelines outlined in Table 2 can be implemented when the containment is completely sealed and is under negative pressure relative to the surrounding area.
Full Containment
Full containment is recommended for the cleanup of mold-contaminated surface areas greater than 100 ft² or in any situation in which it appears likely that the occupant space would be further contaminated without full containment. Double layers of polyethylene should be used to create a barrier between the moldy area and other parts of the building. A decontamination chamber or airlock should be constructed for entry into and exit from the remediation area. The entryways to the airlock from the outside and from the airlock to the main containment area should consist of a slit entry with covering flaps on the outside surface of each slit entry. The chamber should be large enough to hold a waste container and allow a person to put on and remove PPE. All contaminated PPE, except respirators, should be placed in a sealed bag while in this chamber. Respirators should be worn until remediators are outside the decontamination chamber. PPE must be worn throughout the final stages of HEPA vacuuming and damp-wiping of the contained area. PPE must also be worn during HEPA vacuum filter changes or cleanup of the HEPA vacuum.
[10] For example, a remediator may decide that a small area that is extensively contaminated and has the potential to distribute mold to occupied areas during cleanup should have full containment, whereas a large wall surface that is lightly contaminated and easily cleaned would require only limited containment.
Sidebar: Containment Tips
- Always maintain the containment area under negative pressure.
- Exhaust fans to outdoors and ensure that adequate makeup air is provided.
- If the containment is working, the polyethylene sheeting should billow inwards on all surfaces. If it flutters or billows outward, containment has been lost, and you should find and correct the problem before continuing your remediation activities.
Photo caption: Containment Area
Photo caption: Photo 8: Full containment on large job
Citation: EPA 402-K-01-001, Containment, pp. 21–23.
Read on the official site ↗ See it in the full EPA 402-K-01-001
Citations
- EPA 402-K-01-001, Mold Remediation in Schools and Commercial Buildings — Containment, pp. 21–23. Best practice Publisher's page ↗